      Home>>HSM1 Series Moulded Case Circuit Breaker
      • Complete sets of equipment
        • Low Voltage Complete-set Switchgear Equipment
        • High Voltage Complete-set Switchgear Equipment
        • Prefabricated substation
      • Low-voltage distribution
        • surge protector
        • automatic transfer switch automatic switch
        • Intelligent instrument
        • Intelligent Type Air Circuit Breaker
        • Moulded Case Circuit Breaker
          • Thermal Magnetic Moulded Case Circuit Breaker
          • Intelligent Type Moulded Case Circuit Breaker
          • Residual Current Circuit Breaker
        • Switch Disconnector
        • End Terminal Appliances
      • Medium voltage distribution
        • Vacuum circuit breaker
      • Industrial control and protection
        • AC contactor
        • motor protector
        • control and protection switch
        • series thermal overload Relay
      • New energy
      • Email hsdq@188.com
        • Technical 0571-82699110
        • Sales 0571-82699109
        • Service 0571-82600655

      HSM1 Series Moulded Case Circuit Breaker

      Description

      HSM1 series moulded case circuit breaker is competently applied in AC 50Hz electrical circuit with rated insulation voltage 800V, rated voltage up to 690V and rated current 10A~ 800A for power distribution against damage due to overload, under voltage, short circuit, in normal conditions, such MCCB may used for infrequent Closing and opening. Those with rated current up to 400A may be used as a protective apparatus for squirrel-cage motors with infrequent start, breaking during operation as well as the motor overload, short circuit and under voltage.

      DownloadHSM1 Series Moulded Case Circuit Breaker
      Tags
      • Low voltage distribution
      • Product Detail
      • Parameters

      The series circuit breakers possesses seven rated frames: 63A、125A、250A、400A、630A、800A, the current specification 12.5 A ~ 800 A.

      • limited short circuit breaking capacity can be divided into E type (Economical), S type (Typical), M type (Middle and high breaking type), H type (High breaking type), L type (current limiting type);
      • All series circuit breaker can be installed horizontally (lateral), vertical (vertical) and horizontal installation;
      • Whole series of breaker with isolation function
      • The circuit breaker meet the use requirements of installation site with the altitude not exceeding 4000 meters above sea level (need correcting when the altitude above 2000 meters).
      • The outlet and inlet of circuit breaker with protective cover
      • The breaker can be divided into Electricity and motor protection by purpose.
      • Working conditions

      The surrounding medium temperature ranging from -5℃ to +40℃, average value within 24 hours not over +35℃.

      Altitude not exceeding 4000 meters above sea level (need correcting when the altitude above 2000 meters).

      Relative humidity of installation site not over 50% at an ambient temperature of +40℃ yet higher humidity is permissible at lower temperature, e.g. 90% at 20℃(humid type circuit breaker at 25℃ is 95%), Particular measures should be taken for occasional condensation due to temperature fluctuation.

      Pollution grade: 3

      Ⅲ for primary circuit of MCCB and coils of undervoltage releases and Ⅱ for auxiliary circuits and control circuits.

      Humid type circuit breaker can affected by damp and hot, salt fog, fog bacteria.

      The MCCB should be installed in places where there is no potential explosion risk nor electric conducting dust, nor metal corrosion and insulation damage situations.

      The MCCB should be installed in places where there is no rain and snow.

      Type HSM1-63 HSM1-125 HSM1-160 HSM1-250 HSM1-400 HSM1-630 HSM1-800
      Breaking grade S H E S M H E S H L S M H L S M H L S M H S M H
      Rated current A 10/12.5/16/20/32/40/50/63 12.5/16/20/25/32/40/50/63/80/100/125 16/20/32/40/50/63/80/100/125/160 100/125/160/180/200/225/250 200/225/250/315/350/400 400/500/630 500/630/700/800
      Pole number 3/4
      Rated insulation voltage V 800
      Rated impulse withstand voltage V 8000
      Rated voltage 400、690
      Flashover distance 0 <30 <50 0 <50 0
      Rated limited short circuit breaking capacity kA AC400V 25 35 15 25 35 50 25 35 50 80 35 50 65 85 35 50 65 85 50 65 80 50 65 80
      AC690V / / / / / 20 / / 20 / / / 20 / / / 20 / / / 20 / / 30
      Rated service short circuit breaking capacity kA AC400V 25 35 7 16 25 50 25 18 42 50 18 30 48 60 18 30 48 60 30 48 60 30 48 60
      AC690V / / 10 / / 10 / / / 10 / / / 10 / / / 10 / / 20
      Operating performance(life) times load 8000 8000 8000 8000 7000 7000 7000
      Without load 20000 20000 20000 20000 10000 10000 10000
      boundary dimension(Wide* high*deep) three-pole 72×120×70 76×120×70(80) 90×120×70(80) 105×170×103.5 140×254×103.5 210×268×103.5 210×268×103.5
      four-pole 95×120×70 101×120×70(80) 120×120×70(80) 140×170×103.5 184×254×103.5 280×268×103.5 280×268×103.5

      Related Products

      HSQ6 series automatic transfer switch automatic switch
      Excitation drive to achieve the rapid conversion of the PC class two automatic transfer switch
      More
      HSL2 Series Residual Current Circuit Breaker
      HSL2 series Residual Current Circuit Breaker is competently applied in AC 50Hz electrical circuit with rated insulation voltage 690V, rated voltage 400V and rated current 16A~ 630A for electric shock…
      More
      HSU8 series surge protector
      HSU8 series surge protector is suitable for the voltage power supply cabinets, power distribution cabinets, ac distribution panel, power distribution box, lighting box and some important equipment of power into…
      More
      HSM2E Series Moulded Case Circuit Breaker
      HSM2E series moulded case circuit breaker is competently applied in AC 50Hz electrical circuit with rated insulation voltage 800V, rated voltage up to 400V and rated current 16A~ 800A for…
      More
      • HangShen mobile website Latest news on mobile phone
      • HangShen wechat Scan with Wechat app
      • Products
        • Low-voltage distribution
        • Medium voltage distribution
        • Industrial control and protection
        • New energy
        • Complete sets of equipment
      • Download
        • Product sample
        • Manual of the modeling
        • Instruction book
        • Communication protocol
      • About Us
        • Brief introduction
        • “Hangshen” image
        • Technological innovation
        • Technical quality
        • Enterprise reputations
        • Enterprise culture
      • Contact Us
      Copyright 2016© HangShen Electric All Rights Reserved. ICP14040535-3
      Web Development by Anttoweb Web Design.
      WordPress Image Lightbox Plugin
      av大片_伊人网站_无码乱伦_一级爱爱片
      <abbr id="44ww6"><strong id="44ww6"></strong></abbr>
        <dl id="44ww6"><tbody id="44ww6"></tbody></dl>
          <del id="44ww6"><kbd id="44ww6"></kbd></del>
          <abbr id="44ww6"></abbr>
          <kbd id="44ww6"><optgroup id="44ww6"></optgroup></kbd>
          <button id="44ww6"></button>
          <samp id="44ww6"><optgroup id="44ww6"></optgroup></samp>